Polyplumb Underfloor Heating Installation Guide
There are six stages to successfully jointing
the Polyplumb system. These instructions
apply to Polyplumb when used in hot and cold
water or heating applications, including under
floor central heating.
1a. Cutting Polyplumb pipe
Always use one of the approved pipe cutters
(Code PB777). A slight rotation of the pipe when cutting will
help make the operation easier. Never use a
hacksaw. Wherever possible, cut on a depth
insertion mark, these “K” shaped marks are
equally spaced along the pipe and indicate
the depth required for full insertion into a
Polyplumb socket fitting.
1b. Cutting Copper Pipe for insertion into a Polyplumb fitting
Wherever possible, use a rotational pipe
cutter when cutting copper pipe. Ensure that
all cut ends have a rounded lead in, with
burrs removed. Never use a hacksaw. You will
need to mark the depth insertion on the pipe,
the insertion depths are shown in the table.
| Pipe Diameter (mm) |
10 |
15 |
22 |
28 |
| Insertion Depth (mm) |
22 |
27 |
30 |
35 |
2. Use of pipe stiffener
Pipe stiffeners are an integral part of the
joint when using Polyplumb pipe with either
Polyplumb fittings or compression fittings
and need to be fully inserted in to the pipe
end. They are not required when using
copper pipe.
3. Visual check of fitting & fitting
components
Although every single socket is visually
checked during the manufacturing process to
ensure that all components are present and in
the correct order, a further visual check is
recommended as tampering by others can take
place on site or during distribution. The cap
should be hand tight only.
Caution - Do not insert fingers into the
Polyplumb fittings, as the grab ring is sharp
and designed to grip.
Note: Components shown in dismantling
section.
4. Insert pipe fully into fitting
The pipe should be inserted into the fitting
to full socket depth such that the insertion
depth mark aligns with the outer end of the
cap nut on the fitting.
5. Grab ring check
A quick tug on the pipe will confirm that the
pipe is inserted past the grab ring and that a
grab ring was present in the fitting. It does
not however ensure that the pipe is fully
inserted as this can only be confirmed by
using the depth insertion mark.
6. Avoidance of Re-jointing - WARNING!
On no account should a pipe be removed from a jointed Polyplumb fitting by removing
the cap-nut and withdrawing the pipe end
complete with all the socket components
from the fitting to be rejointed without
removing and replacing the grab-ring into
the fitting and re-making the joint in
accordance with the normal Polyplumb
jointing procedure.
If the pipe end complete with all the socket
components is subsequently re-jointed into
the body of a fitting, there is a risk that the
outer edge of the grab-ring could catch on
the outer end or the inside surface of the
socket of the fitting which forces the grabring
into an angled position on the pipe.
Forcing the grab-ring into an angled position
on the pipe in this way, seriously damages
the grab-ring teeth and will reduce the pullout
performance of the joint when subjected
to pressure, such that premature failure will
almost certainly occur. |