Lawson Industrial Fuse Links with Bolted Connections


400/415 Volt Industrial Fuse-Links with Bolted Connections to BS88: Part 2
NIT Industrial Fuse LinkIEC60269-2
EN60269-2
Rated voltages: 415V a.c., 250V d.c. Breaking range and utilization category:gG
Rated breaking capacities: 80kA at 415V a.c, 40kA at 250V d.c.

Lawson Type “ N” & “T” fuse-links are for use in industrial installations and can be fitted into BS88 bolted fuse-holders and distribution fusegear. The range includes all BS88: Part 2 reference fuse-links up to 800 Amps and has gG classification, ensuring compliance with the current edition of the UK Wiring Regulations. Many non-reference tag variants are available to cater for installation in non-standard or specialised equipment.

The range has a rated voltage of 415V a.c. and has been certified at a test recovery voltage of at least 110%. These fuselinks are therefore suitable for use on systems with voltages up to 457V a.c.The range also has a rating of 250V d.c. A complementary range of solid / neutral links is available to suit our fuse-link range.

List Reference
Current Rating (A)
BS88 Reference
Voltage Rating (V)
Breaking Capacity (kA)
BS Standard
IEC Standard
NIT
2, 4, 6, 10, 16, 20, 25, 32
A1
415a.c. 240d.c.
80kA-a.c. 40lA-d.c.
BS88 : Part 2
60269-2
GTIA
2, 4, 6, 10, 16, 20, 25, 32
A2
TIA
2, 4, 6, 10, 16, 20, 25, 32
A2
TIS
35, 40, 50, 63
A3
TIS
80, 100, 125
A3
TCP
6, 10, 16, 20, 25, 32
A4
TCP
40, 50, 63, 80, 100
A4
TFP
125, 160, 200
(as A4)
85TM
200, 250, 315, 355, 400
-
86TT
450, 500, 560, 630
-
86TT
670, 710, 750, 800
-

 

Lawson - More Info
Acrobat Lawson Fuses
Domestic Plug Fuses
Consumer Unit Fuse Links
General Purpose Fuse
House Service Cut Out Fuse Links
Compact Fuse Links
Fuse Link Application Data
DO&D Bottle Fuse Links Comparison
HRC Cartridge Fuse Links Comparison
Cylindrical Cartridge Fuse Links Comparison
HRC Cartridge Fuse Links Comparison