Lawson Fuses Application Data
One of the long standing advantages of fuse protection is that
fuse selection is relatively simple and effective.
The following notes should cover the majority of applications.
Reference should also be made to the appropriate Wiring
Installation rules, such as the IEE Wiring Regulations for Electrical
Installation of buildings (BS7671) which aligns with IEC60364.
Circuit Loading
The current rating of the fuse-link should not be less than the full
load current of the circuit. The circuit should be so designed that
small overloads of long duration will not be of frequent occurrence.
Protection Against Electrical Shock
The rules for pro tection against indirect contact are given in
Chapter 41 of the wiring regulations. For a TN System a
disconnecting time not exceeding 5 seconds is permitted for a
distribution circuit. The maximum values of each fault loop
impedance (Zs) of 240V for gG fuse-links to BS88: Parts 2 and 6 are
shown below.
Rating (A) |
Zs (Ohms) |
Ratings (A) |
Zs (Ohms) |
6 |
14 |
100 |
0.44 |
10 |
7.7 |
125 |
0.35 |
16 |
4.3 |
160 |
0.27 |
20 |
3.0 |
200 |
0.20 |
25 |
2.4 |
250 |
0.16 |
32 |
1.9 |
315 |
0.13 |
40 |
1.4 |
400 |
0.092 |
50 |
1.1 |
500 |
0.067 |
63 |
0.86 |
630 |
0.056 |
80 |
0.60 |
800 |
0.035 |
Ambient Temperature
Above an ambient of 40ºC a general de-rating of 0.5% of the
fuse-link rated current per excess degree ce ntigrade is
recommended.
Breaking Capacity
The standardized values of Breaking Capacity for fuse-links to
BS88 are 80kA for voltages of 415V a.c., and above, and 40kA for
d.c., applications. The 240V a.c., designs have a breaking capacity
of 16kA minimum.
Harmonised Voltage Ratings
The voltage ratings of all Lawson fuses are compatible with
the proposed harmonised voltage ratings of 230V a.c. , 400V a.c.,
and 690V a.c.
Discrimination
All fuse-links to BS88 have a discrimination ratio of 1.6: I. For
example, an upstream fuse-link rated at 160A will discriminate
with a downstream fuse-link rated at 100A.
Current and Energy Limitation
The Lawson range of fuse-links have pre-arcing I2t values
towards the lower limits of BS88 ensuring excellent current
and energy limitation. They also have power losses at rated
current significantly lower than the standardized limits which
assists in the appropriate interchangeability with other make s
of fuse-links.
Cable Ratings and Protection
Lawson fuse-links with gG chara cte ristics pro te ct assoc i ate d
cables against both overload and short circuit currents, provided
that the current rating of the fuse-link In is equal to or less than
the current carrying capacity of the cable Iz.
There is an increasing move away from 70ºC pvc insulation to
materials, which are more environmentally friendly for example
90ºC XLPE. The ratings of fusegear, switches, accessories etc. are
generally based upon the equipment being connected to
conductors intended to be operated at a temperature not
exceeding 70ºC in normal service.
In view of the above it is recommended that the practice of
designs based upon conductor temperatures of 70ºC be
regarded as the norm. In accordance with the Wiring Regulations,
the equipment manufacturer should be consulted to ascertain
the reduction of nominal current rating of the equipment if
conductor temperatures exceeding 70ºC are used.
Cable Size |
Max. Fuse Rating |
(mm2) |
K=115 A |
K=143 A |
1 |
16 |
16 |
1.5 |
20 |
25 |
2.5 |
32 |
32 |
4 |
50 |
50 |
6 |
63 |
63 |
10 |
100 |
125 |
16 |
125 |
160 |
25 |
200 |
250 |
35 |
315 |
355 |
50 |
400 |
500 |
70 |
560 |
630 |
95 |
710 |
800 |
120 |
800 |
1000 |
In motor circ u i t s, the motor starter provides the ove rl o a d
protection and the fuse-link provides the short circuit protection.
The maximum size of fuse-link that can be used depends upon
the type of cable used and is determined in accordance with the
Wiring Regulations using the appropriate K factor.The table gives
the maximum sizes of fuse-links that are recommended for two
popular cables with copper conductors, 70ºC pvc (K = 115) and
90ºC thermo-setting (K =143).
Transformers
When fuse-links are used on the primary side of transformers the
normal current rating of the fuse-link should be at least twice the
nominal transformer primary current.
Fluorescent Lighting
The normal current rating of the fuse-link should be at least twice
the normal full load current of the maximum number of lights to
be switched simultaneously.
Capacitor Circuits
In capacitor circuits, eg. power factor correction, the fuse-link
should be chosen with a current rating greater than 1.5 times the
rated capacitor current. This takes account of the high transient
inrush current, circuit harmonics and capacitor tolerances.
Type 2 Co-ordination
Motor starter manufacturers recommend the fuse-link rating
that can be used in conjunction with motor starters. These
recommendations usually do not state any specific fuse-link
manufacturers type number and they often refer to gG
fuse-links in accordance with IEC 60269 or the equivalent
national standards e. g. BS88: part 2. This gives a simple and
effective means of co-ordination since a fuse-link selected in
accordance with manufacturers’ recommendations to
withstand inrush currents will normally give adequate short
circuit protection to the motor starter.

|