Compact Dimension Fuse Links
230/240 Volt and 400/415 Volt Compact Dimension Fuse-Links to BS88: Pa rt 6 • IEC60269-2
Rated voltages: 240V a.c. and 415V a.c.
Breaking range and utilisation category:gG
Rated breaking capacities: 20kA at 240V a.c.and 80kA at 415V a.c.
Compact Type “CDS” fuse-links are for use in single or three phase
commercial and industrial installations and can be fitted into
BS88 bladed type fuse-holders and distribution fusegear.
The Lawson CLIPFIT range has rated voltages of 240V a.c. or
415V a.c. and has been ce rtified at a test re cove ry voltage of
at least 110%. These fuse-links therefore are suitable for use
on systems with voltages up to 264 or 457V a.c. The rated
and test voltages also ensure that the range meets all
the transitional voltage requirements specified within
the harmonised nominal voltages of 230/400V a.c.
A complementary range of solid/neutral links is available to suit
our fuse-link range.
| List Reference |
Current Rating (A) |
BS88 Reference |
Voltage Rating (V) |
Breaking Capacity (kA) |
BS Standard |
IEC Standard |
| SS |
|
E1 |
240a.c. |
20kA-a.c. |
BS88:Part 6 |
60269-2 |
| NS |
|
F1 |
415a.c. |
50kA-a.c. |
| MES |
10,16,20,25,32,40,50,63 |
F2 |
415a.c. |
80kA-a.c. |
|