|
Fluke
As distribution systems and loads
become more complex, the
possibilities of transient overvoltages
increase. Motors, capacitors and
power conversion equipment such as
variable speed drives can be prime
generators of spikes. Lightning
strikes on outdoor transmission lines
also cause extremely hazardous
high-energy transients. If you’re
taking measurements on electrical
systems, these transients are invisible” and largely unavoidable
hazards. They occur regularly on
low-voltage power circuits, and can
reach peak values in the many
thousands of volts. To protect you
against transients, safety must be
built into the test equipment.
Who Develops Safety Standards?
The IEC (International Electrotechnical
Commission) develops international general
standards for safety of electrical equipment
for measurement, control and laboratory use.
IEC61010-1 is used as the basis for the
following national standards:
- US ANSI/ISA-S82.01-94
- Canada CAN C22.2 No.1010.1-92
- Europe EN61010-1:2001
Overvoltage Installation Categories
IEC61010-1 specifies categories of
overvoltage based on the distance the piece
of equipment is from the power source
(see Fig. 1 and Table 1) and the natural
damping of transient energy that occurs in an
electrical distribution system. Higher categories
are closer to the power source and require
more protection.
Within each installation category there are
voltage classifications. It is the combination of
installation category and voltage classification
which determines the maximum transient
withstand capability of the instrument.
IEC 61010 test procedures take into account
three main criteria: steady-state voltage,
peak impulse transient voltage and source
impedance. These three criteria together will
tell you a multimeter’s true voltage withstand
value.
Within a category, a higher working voltage”
(steadystate voltage) is associated with a
higher transient, as would be expected. For
example, a CAT III 600 V meter is tested
with 6000 V transients while a CAT III 1000 V
meter is tested with 8000 V transients.
So far, so good. What is not as obvious is the
difference between the 6000 V transient for
CAT III 600 V and the 6000 V transient for
CAT II 1000 V. They are not the same.
This is where the source impedance comes
in. Ohm’s Law (Amps = Volts/Ohms) tells us
that the 2 Ω test source for CAT III has six
times the current of the 12 Ω test source for
CAT II. The CAT III 600 V meter clearly offers
superior transient protection compared to the
CAT II 1000 V meter, even though its socalled
“voltage rating” could be perceived as
being lower. See Table 2.
Independent testing is the key to
safety compliance
How can you tell if you’re getting a genuine
CAT III or CAT II meter? Unfortunately it’s not
always that easy. It is possible for a
manufacturer to self-certify that its meter is
CAT II or CAT III without any independent
verification. The IEC (International
Electrotechnical Commission) develops and
proposes standards, but it is not responsible
for enforcing the standards. Look for the
symbol and listing number of an independent
testing lab such as UL, CSA, VDE, TÜV or
other recognized approval agency.
These symbols can only be used if the product
successfully completed testing to the agency’s
standard, which is based on national/-
international standards. UL 3111, for example,
is based on EN61010-1. In an imperfect world,
this is the closest you can come to ensuring
that the meter you choose was actually tested
for safety.
| Overvoltage Category |
In Brief |
Examples |
| CAT IV |
Three-phase at utility connection, any outdoor conductors |
• Refers to the “origin of installation”; i.e., where low-voltage connection is made to utility power.
• Electricity meters, primary overcurrent protection equipment.
• Outside and service entrance, service drop from pole to building, run between meter and panel.
• Overhead line to detached building, underground line to well pump. |
| CAT III |
Three-phase distribution, including single-phase commercial lighting |
• Equipment in fixed installations, such as switchgear and polyphase motors.
• Bus and feeder in industrial plants.
• Feeders and short branch circuits, distribution panel devices.
• Lighting systems in larger buildings.
• Appliance outlets with short connections to service entrance. |
| CAT II |
Single-phase receptable connected loads |
• Appliance, portable tools, and other household and similar loads.
• Outlet and long branch circuits.
• Outlets at more than 10 meters (30 feet) from CAT III source.
• Outlets at more than 20 meters (60 feet) from CAT IV source. |
| CAT I |
Electronic |
• Protected electronic equipment.
• Equipment connected to (source) circuits in which measures are taken to limit transient
overvoltages to an appropriately low level.
• Any high-voltage, low-energy source derived from a high-winding resistance transformer,
such as the high-voltage section of a copier. |
Safety is everyone’s responsibility
but ultimately it is in your hands.
No tool by itself can guarantee your
safety when working with electricity.
It’s the combination of the right tools
and safe work practices that gives
you maximum protection. Here are a
few tips to help you in your work:
Make sure you always comply with (local)
regulations.
Work on de-energized circuits whenever
possible.
Use proper lock-out/tag-out procedures. If these
procedures are not in place or enforced, assume
that the circuit is live.
Use protective gear when working on
live circuits:
- Use insulated tools
- Wear safety glasses or a face shield
- Wear insulated gloves, remove watches or jewelry
- Stand on an insulated mat
- Wear flame resistant clothing, not ordinary work clothes
Select the right test tool:
- Choose a test tool rated to the highest
category and voltage for which it could possibly be used (most often 600 or 1000 volt CAT III and/or 600 volt CAT IV).
- Look for the category and voltage marking
near the recessed input connectors of your
test tool and a “double insulated” symbol on the back.
- Verify your test tool has been tested and
certified by two or more independent testing
laboratories, such as UL in the United States
and VDE or TüV in Europe by looking for the symbols of these agencies on (the back of) your test tool.
- Make sure that the test tool is made of a high-quality, durable non-conductive material.
- Check the manual to verify that the ohms,
continuity and capacitance circuits are
protected to the same level as the voltage
test circuit, to reduce hazards when the test tool is used incorrectly in ohms, continuity or capacitance mode (if applicable).
- Verify that the test tool has internal
protection to prevent instrument damage
when voltage is incorrectly applied to an amperage measurement function (if applicable).
- Make sure that the amperage and voltage of
your test tool’s fuses meets specifications.
Fuse voltage must be as high or higher than
the test tool’s voltage rating.
- Be sure to use test leads that have:
- Shrouded connectors
- Finger guards and a non-slip surface
- Category ratings that equal or exceed those of the test tool
- Double insulation (look for the symbol)
- A minimum of exposed metal on the probe tips
Inspect and test your test tool:
- Check for a broken case, worn test leads or a faded display.
- Make sure the batteries still deliver sufficient
power to get reliable readings. Many test tools have a low battery indicator on the display.
- Check the test leads resistance for internal breaks while moving the leads around (good leads measure 0.1-0.3 Ohm).
- Use the meter’s own test capability to ensure that the fuses are in place and working right (see manual for details).
Apply the appropriate working
practices when measuring on live
circuits:
- Hook on the ground clip first, then make
contact with the hot lead. Remove the hot
lead first, the ground lead last.
- Use the three-point test method, especially
when checking to see if a circuit is dead.
First test a known live circuit. Second, test
the target circuit. Third, test the live circuit again. This verifies that your test tool worked properly before and after the measurement.
- Hang or rest the test tool if possible. Try to avoid holding it in your hands, to minimize personal exposure to the effects of transients.
- Use the old electrician’s trick of keeping
one hand in your pocket. This lessens the change of a closed circuit across your chest and through your heart.
Overvoltage Installation Category |
Working Voltage (DC or AC RMS to ground) |
Peak Impulse Transient (20 repetitions) |
Test Source (Ω = V/A) |
CAT I |
600 V |
2500 V |
30 Ohm source |
CAT I |
1000 V |
4000 V |
30 Ohm source |
CAT II |
600 V |
4000 V |
12 Ohm source |
CAT II |
1000 V |
6000 V |
12 Ohm source |
CAT III |
600 V |
6000 V |
2 Ohm source |
CAT III |
1000 V |
8000 V |
2 Ohm source |
CAT IV |
600 V |
8000 V |
2 Ohm source |
|
|